Received: January 16, 2025
Accepted: July 02, 2025
Available: August 19, 2025
The residential sector represents a significant part of energy consumption in tropical countries, where the climate directly influences the demand for ventilation and air conditioning. In cities like Bucaramanga (Colombia), the growth of building stock and the increased use of electrical appliances highlight the need for energy efficiency strategies. Although Colombia has made regulatory progress—such as Resolution 0549 of 2015—its application in residential buildings, especially in warm climates, remains underexplored. This study analyzes the impact of energy-saving measures on the demand profile of a middle-income residential building located in a tropical warm climate. The implementation of strategies recommended by Resolution 0549-2015 was evaluated through energy simulations using DesignBuilder V6. The methodology considered five scenarios: an existing building, one representing typical features of the current building stock, and three others that incorporate horizontal shading, natural ventilation, and variations in the window-to-wall ratio. The results showed a 20% reduction in energy consumption in the existing building compared to the reference model, mainly due to improvements in lighting and elevator efficiency. It is concluded that the proposed energy-saving measures are effective only when air conditioning systems are present and that their implementation can help reduce transformer loads. This study offers a valuable local contribution, being one of the first in Colombia to examine residential building design from an energy efficiency perspective, based on national regulations and simulation tools.
Keywords: Building energy simulation, energy conservation, energy demand, energy efficiency, residential buildings.
El sector residencial representa una parte importante del consumo energético en países tropicales, donde el clima influye directamente en la demanda de ventilación y climatización. En ciudades como Bucaramanga (Colombia), el crecimiento del parque inmobiliario y el mayor uso de equipos eléctricos hacen necesaria la adopción de estrategias de eficiencia energética. Aunque Colombia ha avanzado en normativa, como la Resolución 0549 de 2015, su aplicación en viviendas, especialmente en climas cálidos, ha sido poco estudiada. Este trabajo analiza el impacto de medidas de ahorro energético sobre el perfil de demanda de una edificación residencial de ingresos medios ubicada en clima tropical cálido. Se evaluó la implementación de estrategias sugeridas por la Resolución 0549-2015 mediante simulaciones energéticas en DesignBuilder V6. La metodología consideró cinco escenarios: un edificio existente, uno con características del parque inmobiliario actual y tres que integran sombreado horizontal, ventilación natural y variaciones en la relación ventana-pared. Los resultados mostraron una reducción del 20 % en el consumo energético del edificio existente respecto al de referencia, principalmente por mejoras en iluminación y ascensores. Se concluye que las medidas propuestas tienen efecto sobre el consumo, solo cuando hay sistemas de aire acondicionado, y que su implementación puede reducir la carga en los transformadores. Este estudio representa una contribución local relevante al ser uno de los primeros en Colombia que examina el diseño de viviendas desde un enfoque de eficiencia energética, apoyado en normativa nacional y simulación computacional.
Palabras clave: Simulación energética de edificaciones, conservación de energía, demanda energética, eficiencia energética, edificaciones residenciales.
Buildings are one of the sectors that consume the most energy worldwide
Energy efficiency effectively reduces building energy consumption and addresses sustainable development and climate change mitigation efforts. Widespread adoption of energy-saving measures in buildings reduces overall energy use and helps countries achieve emission reduction targets
In Colombia, recently, the Ministry of Housing, City, and Territory (Ministerio de Vivienda, Ciudad y Territorio - MVCT) established Resolution 0549 of 2015 (R0549-2015)
For their part,
Other studies have investigated the incorporation of energy-saving measures in buildings. In 2017
On the other hand,
In 2024,
In Colombia, case studies on energy efficiency strategies applied to specific buildings are scarce. Most identified research has focused on the analysis of public policies and literature reviews. However, recent progress has been reported with an energy characterization study conducted on 20 residential and office buildings in Bucaramanga
Moreover, one of the most relevant national studies examines sustainable construction scenarios and the adoption of energy efficiency standards in the cities of Bogotá, Medellín, Cali, and Barranquilla. Using a dynamic model with monthly resolution for the period 2015–2035, a high level of compliance was identified in Bogotá (around 70%), while in Cali and Barranquilla many companies remain unaware of current regulations
Additionally, another study addresses the conditions facilitating the implementation of energy efficiency policies in buildings in Brazil, Chile, Colombia, and Uruguay. The authors conclude that literature on enabling frameworks in developing countries is scarce, highlighting Chile and Uruguay as having the most favorable environments. In contrast, Colombia faces significant distortions in energy pricing, which hinders progress in this field
Regarding thermal comfort, a review of the state of research in the country reveals limited academic output, mostly concentrated around 2012. Residential buildings are the most studied typology, followed by schools and offices
The literature includes several studies that analyze the behavior of the demand curve in buildings
Although some studies focus in detail on individual dwellings, there is a notable lack of research centered on tropical multifamily buildings with limited use of artificial air conditioning. As mentioned earlier, incorporating energy-saving measures can enhance both the energy performance and thermal comfort of buildings. Furthermore, the widespread adoption of such measures may positively impact electrical system planning by lowering energy demand, increasing system stability, and supporting the integration of renewable energy sources.
Despite this, there is still a gap in the literature regarding studies that assess how the integration of energy-saving measures affects energy demand in residential buildings. This gap limits the ability to fully understand the potential benefits of these measures in transforming both the residential sector and the operation and planning of electrical systems.
With respect to the energy-saving measures analyzed, previous studies have mainly focused on measures related to air conditioning systems and their interaction with thermal storage
Therefore, the objective of this work was to evaluate the impact of a set of energy-saving measures on the demand curve of a residential building. The building analyzed is a middle-income multifamily dwelling located in Bucaramanga, Colombia—a city representative of both the tropical climate and national construction practices. The analysis includes five scenarios that incorporate the energy-saving measures recommended by the prescriptive method outlined in Resolution R0549-2015 for residential buildings in hot-dry climates. This method aims to meet energy-saving targets defined by the implementation of the measures listed in Tables 16 to 19 of Annex 1 of the Resolution [19]. Investigating this topic can provide valuable insights for network operators regarding the potential future operating conditions of the electrical grid.
The study starts by obtaining the energy model of the selected building (scenario 0). The actual model allowed four additional analysis scenarios to be received. The reference building or baseline (scenario 1) and three scenarios (2, 3, and 4) later consider integrating energy-saving measures. Finally, the results of the energy simulations allow a comparative analysis to determine the impact of incorporating such a strategy on the building's power demand curve. Figure 1 presents the schematic of the study methodology.
2.1 Description of the building under study
This study takes place in the Metropolitan Area of Bucaramanga (Área Metropolitana de Bucaramanga – AMB), situated at 7.13° N latitude and 73.13° W longitude. The region experiences an average solar irradiation of 4.8 kWh/m² per day. Characterized by a warm tropical climate, the city is located at an elevation of 960 meters above sea level. Table 1 summarizes the main climatic characteristics of this tropical location
| Parameter | Value |
| Average annual precipitation | 1279 mm |
| Average ambient temperature | 24°C (During the day) |
| 27°C (Sunlight hours) | |
| Average maximum temperature | 31°C |
| Average solar irradiation | 4.8 kWh/m2∙day |
| Wind speed | 1.0-1.5 m/s |
This building is a type of multifamily, half-income housing. It has twelve floors, each housing six three-bedroom apartments with an average area of 62 m2. Table 2 presents the building's construction characteristics.
| Characteristic | Value / Details |
| Construction system | Industrialized with a structure of plates and concrete walls |
| Approximate WWR | 19 |
| Exterior walls configuration | The wall is concrete, putty, and painted inside, and the plastic stucco is outside. Overall thickness: 13 cm |
| Exterior walls U value [W/m²·K] | 3.25 |
| Roof configuration | Solid concrete plate, stucco, and lower face paint. Mortar, asphalt layer, and reflective paint on the upper face. Overall thickness: 16 cm |
| Cover U value [W/m²·K] | 2.76 |
| Lighting power density - LPD [W/m2] | 2.22 |
| Power Density of plug-in charges [W/m2] | 31.49 |
| Average power consumption [kWh/m2] | 130 |
| Air conditioning system | The main room of some of the apartment typologies (9000 BTU) |
| Elevators | 1 x 7.5 HP |
| Apartment area [m2] | 4145.0 |
| General services area [m2] | 456.6 |
2.2 Energy modeling
DesignBuilder V6 software enabled the building's energy modeling. This program stands out for its user-friendly graphical interface, integrated simulation modules, high degree of customization through coding, support for certifications and regulations, and extensive documentation and technical support. This process comprises three phases: geometric modeling, model data mapping, and model fitting.
Geometric modeling requires information from floor plans, facade elevations, and door and window details. The model data mapping consists of four categories: building usage data, material data, load data, and HVAC data. Memories of the building's architectural and electrical design and an inspection visit were considered sources of information.
Findings from the inspection visit and historical monthly energy consumption data provided valuable insights into the characteristics and operational dynamics of the building's air conditioning systems. Each apartment's main room has a 9000 BTU split air conditioning unit. Figure 2 presents the energy model of the building under study.
A parameter adjustment process improved the reliability of the building’s energy model. This process involved comparing the simulated annual energy consumption values with the measured data provided by the local energy utility company. For the habitable areas (apartments), the adjustment was based on calculating the percentage error between the measured and simulated consumption. The model was considered calibrated when the error was below 10% in at least 90% of the apartment types.
For common areas, where measured consumption data were not available, the adjustment relied on lighting and motor usage data obtained from modeling exercises of similar buildings.
Refining the usage data of some of the building systems allowed the adjustment of the models. After adjustment, the model error was only 0.06%. For this reason, the energy model is valid for the proposed analyses.
2.3 Evaluation of the impacts of measures
Five (5) simulation scenarios were considered to evaluate the impact of integrating measures. The proposed simulation scenarios consider the building's design characteristics (actual building scenario), the characteristics typical to its typology (reference building scenario), and recommended energy-saving measures for compliance with R0549-2015 that can be modeled in DesignBuilder (strategy integration scenarios).
2.3.1 Actual scenario
This scenario corresponds to the simulation of the energy model of the building under study as it is built. It allows analysis of the impacts of the building's particular design characteristics on the demand curve.
2.3.2 Reference scenario
This scenario consisted of simulating the energy model of the building configured with a group of usual characteristics of the stock. The representative characteristics of the reference scenario are part of the results of an inter-institutional project led by the Construction Cluster of the Bucaramanga Chamber of Commerce
| Characteristics | Value / Detail |
| Building use and operation data | Same as in the actual case |
| Exterior walls | Exterior walls of hollow clay brick core, covered with frieze mortar, interior stucco, and exterior plastic stucco |
| Cover | Roof with a solid concrete core, leveling mortar, asphalt layer on the outside, and plaster inside |
| Glazing | 3 mm glass, U value of 5.91, and SHGC value of 0.8 |
| WWR | The window-to-wall ratio remains the same |
| Appliance and plug-in loads | Same as in the actual case. |
| Elevators load | 18.5 kW |
| Lighting power density | 7.53 W/m2 |
2.3.3 Scenarios with savings measures
There are three in total. These scenarios are associated with three energy-saving measures recommended by R0549-2015 for medium-income residential buildings in hot and dry climates: window-to-wall ratio – WWR, horizontal shading, and natural ventilation. The savings strategy scenarios required three energy models, one for each strategy. Table 4 summarizes the considerations for the simulation scenarios.
| Scenario | Denomination | Scenario considerations | |
| 0 | Actual building | The annual hourly simulation of the energy model was generated according to the design specifications and inspection visit findings. | |
| 1 | Reference building | The annual hourly simulation of the energy model was generated according to the representative characteristics of the stock, as shown in Table 3. | |
| 2 | Actual building + horizontal shading | The annual hourly simulation of the energy model of the actual building was set with horizontal overhangs of 80 cm on the top of the windows. | |
| 3 | Actual building + Natural ventilation | The annual hourly simulation of the energy model of the actual building was configured with natural ventilation in all its spaces. | |
| 4 | Actual building + WWR 30% | The annual hourly simulation of the energy model of the actual building was configured with a WWR ratio of 30% (this percentage was analyzed by the technical document of R0549-2015) | |
The breakdown of the characteristic demand curve allowed the study of the building's actual behavior. Comparing the demand curves permitted the analysis of the scenarios' differences in behavior. The study of the impacts of the different scenarios considered the consumption curves of the principal energy uses.
Likewise, the analyses considered the effects of using the power transformer. The study also compared the energy use intensity indicators obtained for each scenario with the indicators regulated in R0549-2015. Finally, the impact of savings measures was analyzed using the concept of virtual energy.
3.1 Energy consumption results
The analysis began with the evaluation of global energy consumption across the scenarios. Figure 3 presents the total annual energy consumption associated with each simulation scenario. According to the results, the actual scenario has a yearly energy consumption of 130.42 MWh. Appliances and other plug-in loads account for 76.1% of total consumption. Air conditioning and lighting consumption represent 12.8% and 11.1%, respectively.
The actual building's energy performance is like that of the building configured with a WWR of 30% (scenario 4) and that of the building with horizontal shading (scenario 2). These results suggest a negligible impact of these measures on the building's energy savings, possibly due to the nocturnal and sectorized operation of the air conditioning systems.
Applying natural ventilation (scenario 3) reveals more significant energy savings than the other scenarios. The annual energy consumption of the building decreases by approximately 13% in the actual scenario. On the contrary, the Reference building scenario presents the highest annual energy consumption (162.71 MWh). This behavior occurs due to less efficient lighting systems and elevators, which are typical stock characteristics. These systems could be the subject of a technological reconversion campaign that makes it possible to improve the energy efficiency of buildings, from which savings of close to 25% in energy consumption would be achieved in the actual scenario.
Compliance with local efficiency standards (R0549-2015) was also evaluated across the study scenarios. Table 5 presents the comparison of the Energy Intensity Index- EII of each scenario with the base indicator of the regulations, taking into account the hot, dry climate (assigned by the local regulations for the AMB) and the tempered climate (determined as the climate of the AMB from of the results of
| Scn. | kWh/m2/year | Baseline (kWh/m2/year) | Hot-Dry [%] | Tempered [%] | |
| Hot-Dry | Tempered | ||||
| 0 | 30.50 | 36.9 | 48.3 | 17% | 37% |
| 1 | 38.06 | -3% | 21% | ||
| 2 | 30.33 | 18% | 37% | ||
| 3 | 26.60 | 28% | 45% | ||
| 4 | 30.52 | 17% | 37% | ||
According to these results, the natural ventilation scenario represents the highest percentage of savings. When considering AMB in a hot-dry climate, the natural ventilation scenario is the only one to satisfy the minimum savings percentage established by the resolution (25% in a hot-dry and temperate climate). For the other scenarios, meeting the savings goal depends on different measures to achieve an additional 8% savings.
The opposite occurs when considering Bucaramanga in a temperate climate. In this case, the real and strategy integration scenarios satisfy the minimum energy-saving requirement.
From the above, climatic zoning greatly influences the savings percentages. For this reason, studies are needed to verify the climatic zoning assigned to the AMB. By validating climatic zoning, it will be possible to evaluate whether the degree of required savings is difficult to satisfy or if the estimated design has good savings characteristics.
3.2 Results of the actual scenario
Figure 4 presents the demand curves and their respective breakdown in energy uses for the actual scenario on the average day of March, the month with the highest solar irradiation of the year according to the climate file.
According to these results, the highest consumption in a typical day occurs between six in the afternoon and midnight. During this period, the building's highest energy demand occurs due to the intensive use of appliances and plug-ins inside the homes. The lighting and air conditioning systems are used (after 10 p.m.).
Considering the previous results, some measures could be proposed to reduce the building's energy consumption. Firstly, an energy awareness campaign aimed at users could reduce the energy consumption of plug-in appliances and motors. Secondly, additional savings could be achieved by improving the efficiency of air conditioning systems or dispensing with them during the early morning hours, the period with the lowest outside temperatures.
Figure 5 compares the demand curves of the actual building (scenario 0) and the reference building (scenario 1). According to the comparison, the building under study has better energy performance than its reference counterpart. The building under study presents an average reduction of 17% in energy consumption compared to the reference one. The most significant savings can be seen between 9:00 a.m. and 10:00 p.m. This behavior may be related to improvements in the efficiency of elevators and the lighting system of the actual building concerning the reference building. Notably, similar occupancy data was used in both cases, so this is not an influencing factor in the comparison.
3.3 Comparison of the demand curve obtained for the proposed scenarios
Figure 6 compares the time curves of power consumption for the five scenarios presented in Table 4.
As the annual energy consumption results show, the actual scenario (scenario 0) behaves similarly to the scenario with shading (scenario 2) and to the WWR configuration at 30% (scenario 4). This is because there are no appreciable changes in the demand for air conditioning due to the effect of the exterior overhangs since air conditioning use is primarily nocturnal.
On the other hand, increasing the glazing area to 30% (the value recommended by the local standard for medium-income residential buildings) slightly increases the thermal load and, consequently, the air conditioning consumption of air-conditioned spaces. As expected, the natural ventilation scenario does not present consumption due to the absence of artificial air conditioning equipment. Opening windows to satisfy comfort needs in mostly air-conditioned spaces offers an average saving of close to 28% relative to the actual case.
Regarding lighting consumption, the results show a significant variation in behavior in the curve of the Reference building scenario compared to the other scenarios. The hourly energy consumption for lighting in this scenario is approximately 64% higher than the average hourly consumption of the different scenarios. In this case, the lighting could be more efficient.
Equipment consumption behavior is similar in scenarios that consider the characteristics of the actual building. The reference-building scenario presents hourly consumption values that are, on average, 6% higher than those of the other scenarios. This situation occurs due to the use of efficient elevators in the actual building design.
3.4 Transformer loadability analysis
The analysis also included transformer loadability under the different scenarios. Figure 7 presents the results of an analysis of the use of the transformer.
The similarity between the demand curves of the actual building scenario, horizontal shading scenario, and WWR of 30% of the scenario causes the cumulative demand curves to overlap. The power demanded from the transformer for these scenarios in each case is between 10 kVA and 15 kVA most of the time (46%). Under these conditions, the transformer operates at a chargeability of 30%. For the case of Scenario 3 (natural ventilation), the demand was between 5 kVA and 10 kVA most of the time. In this case, the load capacity of the transformer can be reduced by an additional 5%.
3.5 Virtual energy assessment
Previous results do not show the impact of measures such as: horizontal shading on windows and increasing the window-to-wall ratio on the building's energy savings and its respective demand curve. Consequently, the study assessed the impact of these measures and natural ventilation based on the virtual energy concept.
This indicator refers to the potential energy used in the building to guarantee comfort conditions (temperatures within the comfort range of 21 and 25 °C). To calculate virtual energy, a standard air conditioning system was defined by the recommendations of tables G3.1.1-3 and G3.1.1-4 of Appendix G of ASHRAE 90.1 of 2019.
In addition to considering shading measures, increasing WWR to 30%, and natural ventilation, the analysis using virtual energy considered three additional scenarios: a scenario that integrates all the measures considered in this study (All Measures) and the actual (Full Air-Conditioning) and reference (Reference Air-Conditioning) scenarios with integration of virtual energy. Figure 8 presents the demand curves for the scenarios considered in this study section.
The results of the simulations that consider virtual energy show that the scenarios with a WWR of 30% considerably increase a building's energy consumption during the day. This increase occurs due to increased interior thermal gains through the building's glazing. In practice, these results infer deterioration in thermal comfort inside the homes if such WWR values are considered.
On the other hand, the shading and natural ventilation scenarios behave similarly to the actual scenario under the virtual energy configuration. Horizontal shading on windows does little to reduce the building's energy consumption. Unlike the analysis without virtual energy, the scenario with natural ventilation has a negligible impact because, under the virtual energy configuration, natural ventilation does not occur at the user's request but automatically considers the thermal comfort inside the building.
In contrast, the combined use of all measures enables an average hourly reduction of 43% compared to the actual scenario, which occurs thanks to the greater use of natural ventilation due to the increase in the opening area.
Regarding the information used for the analysis, the strategy adopted to evaluate demand curves based on dynamic simulations has been validated multiple times by other researchers using tools such as TRNSYS
Although this study identifies limitations associated with the partial use of the air conditioning system, it is important to note that the scientific literature commonly reports research that quantifies the energy-saving potential of conservation measures under continuous HVAC operation
To address this limitation, the analysis was complemented by the concept of virtual energy. This approach allowed for the evaluation of the potential contribution of passive measures in a scenario where the building would be required to maintain constant thermal comfort conditions (between 21°C and 25°C). In other words, the building’s energy performance was simulated under the assumption of continuous HVAC operation. This made it possible to more clearly identify the impact of strategies such as increasing the window-to-wall ratio or combining multiple measures, which can lead to energy consumption reductions of up to 43%. These effects would not have been evident in simulations based solely on actual usage, where the individual impact of each strategy was more limited.
Another important factor is the official climate zoning assigned to Bucaramanga. This study relied on the classification established by Resolution R0549-2015 (hot-dry climate); however, recent research suggests that the area may be more accurately characterized as temperate. This discrepancy is significant, as regulatory requirements—and the expected savings thresholds—vary by climate zone. Thus, there is a degree of uncertainty that directly affects the evaluation of compliance with the regulation and warrants further examination in future studies.
The definition of the reference building also represents a critical variable. As in other simulation-based studies, the results largely depend on the selected baseline. A poorly defined reference scenario can either exaggerate or underestimate the impact of the evaluated strategies. In this case, efforts were made to construct a representative scenario based on the existing building stock; nonetheless, a certain degree of arbitrariness is inherent in the definition of such references.
Finally, the transformer load analysis was based on average values, providing a general overview but failing to fully capture the dynamic behavior of the electrical system. Future research should consider installed nominal power and hourly load profiles to better understand how these energy-saving measures affect the building’s electrical infrastructure.
In summary, although the limitations identified do not diminish the value of the findings, they do highlight important aspects that warrant further exploration. In particular, future studies could incorporate more comprehensive economic and environmental assessments, as well as improve the resolution of the electrical analysis, to provide a more holistic view of the impact of efficient design strategies in residential buildings located in tropical climates.
The primary determinant of energy consumption in the scenarios analyzed is plug-in equipment, which represents around 75% of total consumption. The presence of efficient elevators and LED lighting in the actual configuration (scenario 0) produces an approximate saving of 20% compared to the reference scenario (scenario 1). This configuration offers a saving of 17% relative to the baseline of R0549-2015, while under temperate climate conditions, savings can reach close to 37%.
Most scenarios that include energy-saving measures (scenario 2 and scenario 4) present only minor changes in energy demand. Compliance with local regulations requires additional measures. The exception is the natural ventilation scenario (scenario 3), which provides the only significant savings under hot-dry weather conditions.
Comparing scenarios reveals the reference scenario as having the highest energy demand. During much of the daytime, hour-by-hour consumption values are similar across scenarios, but significant differences occur during periods of intensive elevator and lighting use.
The results also demonstrate that energy-saving measures can influence transformer loadability. In this study, savings were achieved through design changes—such as improved ventilation and efficient lighting—without investments in new technologies like solar or wind power. While the transformer load analysis used average consumption values, future assessments could benefit from considering the rated power established in the building’s electrical design, a common recommendation for designing distribution networks in residential buildings. Notably, integrating natural ventilation reduces energy demand and limits transformer loadability by nearly 25% of the time.
Finally, virtual energy analysis shows that the use of artificial air conditioning determines the impact of passive measures on a building’s energy consumption. Combining multiple savings measures generally offers better results than implementing individual ones.
The authors thank the Vice-Rectorate for Research and Extension (Vicerrectoría de Investigación y Extensión) from the Universidad Industrial de Santander (Project 3945).
Likewise, thanks to the Construction Cluster of the Bucaramanga Chamber of Commerce (Clúster de Construcción de la Cámara de Comercio de Bucaramanga), which is the entity that supported this research through information on the design and operation of buildings in the Metropolitan Area of Bucaramanga (Área Metropolitana de Bucaramanga).
The authors declare that they have no conflict of interest.
Jorge Cárdenas-Rangel:conceived and designed the experiments, performed the experiments, analyzed and interpreted the data, contributed reagents,
materials, analysis tools, wrote the paper.
Julián Jaramillo-Ibarra:conceived and designed the experiments, performed the experiments, analyzed and interpreted the data, contributed reagents,
materials, analysis tools.
German Osma-Pinto: conceived and designed the experiments, performed the experiments, analyzed and interpreted the data, contributed reagents,
materials, analysis tools