Received: March 17, 2025
Accepted: November 25, 2025
Available: January 13, 2026
The optimization of economic dispatch in hybrid diesel photovoltaic systems within Non-Interconnected Zones (NIZ) is essential to enhance energy sustainability and reduce operating costs. The variability of renewable generation and the uncertainty of electricity demand hinder efficient planning, underscoring the need for advanced optimization models. The purpose of this research was to develop an economic dispatch model for diesel generators integrated with photovoltaic generation, incorporating electricity demand forecasting. The methodology was based on formulating a quadratic programming problem and applying vector autoregressive models supported by socioeconomic variables. Simulations were carried out in Python using the IPOPT (Interior Point Optimizer) solver. The proposed model aimed to optimize operational efficiency by reducing CO₂ emissions and production costs. The analysis was applied to a modified version of the IEEE 33-bus distribution system. The results showed that the optimal dispatch reduced generation costs by 32.1%, decreasing from USD 15 853.83 in the base scenario to USD 10 769.82 with the inclusion of photovoltaic generation. Likewise, daily fuel consumption decreased by 4 227.4 gallons, while CO₂ emissions were reduced by 41 926.1 kg. In addition, solar generation contributed 4 249.2 kWh per day, equivalent to 5.09% of total demand, directly reducing technical losses from 292 kW to 243 kW. In conclusion, the results demonstrate that the integration of predictive models and optimization techniques improves operational performance and supports sustainable energy planning in isolated communities.
Keywords: Autoregressive vectors, energy forecasting, optimization models, photovoltaic systems.
La optimización del despacho económico en sistemas híbridos diésel-fotovoltaico en zonas no interconectadas (ZNI) es clave para potenciar la sostenibilidad energética y reducir costos operativos. La variabilidad de la generación renovable y la incertidumbre en la demanda dificultan una planificación eficiente, lo que resalta la necesidad de modelos avanzados de optimización. El propósito de esta investigación fue crear un modelo de despacho económico de generadores a diésel integrados con generación fotovoltaica, considerando el pronóstico de la demanda eléctrica. La metodología se basó en la formulación de un problema de programación cuadrática y la aplicación de vectores autorregresivos sustentados en variables socioeconómicas. Las simulaciones se realizaron en Python, y el solver IPOPT (Interior Point Optimizer). El modelo buscó optimizar la eficacia operativa, disminuyendo las emisiones de CO₂ y los costos de producción. El análisis se aplicó a una versión modificada del sistema IEEE de 33 nodos. Los resultados mostraron que el despacho óptimo reduce los costos de generación en un 32,1 %, pasando de USD 15 853,83 en el escenario base a USD 10 769,82 con la incorporación de la generación fotovoltaica. De igual forma, se logró una disminución diaria en el consumo de combustible de 4 227,4 galones y una reducción en las emisiones de CO₂ de 41 926,1 kg. Asimismo, la generación solar aportó 4 249,2 kWh por día, equivalente al 5,09 % de la demanda total, contribuyendo directamente a la disminución de las pérdidas técnicas, que pasaron de 292 kW a 243 kW. En conclusión, los resultados demuestran que la integración de modelos predictivos y técnicas de optimización mejora el desempeño operativo y favorece la planificación energética sostenible en comunidades aisladas.
Palabras clave: Vectores autorregresivos, previsión energética, modelos de optimización, sistemas fotovoltaicos.
The continuous rise in global energy demand, coupled with the imperative to reduce carbon emissions, has accelerated the transition toward more sustainable and efficient energy systems. Within this framework, isolated communities encounter significant challenges due to their strong dependence on diesel-based generation, which entails high operating costs and considerable environmental impacts
Optimization-based approaches have emerged as a crucial tool to address these challenges, demonstrating their effectiveness in improving both the planning and operation of hybrid diesel photovoltaic systems
Recent developments combining mathematical programming, time-series simulation, and machine learning techniques have significantly improved the utilization of available energy resources, thereby enhancing system reliability and supply continuity
In parallel, recent studies have underscored the relevance of incorporating predictive models into rural grid management. Approaches based on Markov chains and deep learning architectures have been employed to enhance demand forecasting accuracy, achieving notable reductions in estimation errors
Despite these advances, several research gaps remain that justify the development of the present study. First, many existing optimization models overlook variability in demand estimation, which can adversely affect system performance and operational efficiency
Moreover, few studies have investigated the influence of renewable generation variability on the operational stability of hybrid systems, complicating the design of effective mitigation strategies for intermittency
In response to these gaps, the present research aims to develop and assess an optimization model for the optimal dispatch of diesel photovoltaic generation in isolated communities. The model integrates socioeconomic variables into electricity demand forecasting through the use of vector autoregressive models and computational simulations. The ultimate objective is to formulate an economic dispatch framework that combines diesel generation and photovoltaic inputs while accounting for demand dynamics.
The contribution of this study lies in the design of a comprehensive mathematical model for optimal dispatch in diesel photovoltaic hybrid systems, intended to enhance energy planning and management processes. The proposed methodology incorporates demand forecasting techniques based on socioeconomic indicators, thereby improving the accuracy and applicability of decision making in hybrid microgrids. Unlike conventional approaches that treat demand as a static input or rely exclusively on historical data, this research introduces a dynamic analysis tailored to the real conditions of Non-Interconnected Zones (NIZ) using vector autoregression and computational simulations. This methodological integration enables more efficient energy planning, quantifiable reductions in operational costs and CO₂ emissions, and strengthens the sustainability and feasibility of the energy transition in isolated territories.
The remainder of this article is structured as follows. Section 2 outlines the adopted methodology, detailing the simulation design, computational tools, and mathematical models used in demand forecasting and economic dispatch. Section 3 presents the results and discussion, evaluating the model's performance. Finally, Section 4 provides conclusions on the model's applicability to energy planning.
The proposed methodology seeks to enhance the economic dispatch process through the precise management of short-term power forecasts. The analysis integrates photovoltaic distributed generation (PV-DG) into a modified IEEE 33-node test system, enabling the evaluation of thermal generation dispatch under realistic operating conditions. The entire implementation was carried out in Python using the IPOPT solver to ensure computational efficiency and robustness.
The assessment focuses on key performance indicators such as reductions in generation costs, energy losses, fuel consumption, and CO₂ emissions, as well as improvements in voltage stability and overall system reliability. The methodological framework is structured into several key stages: data acquisition and preprocessing, load simulation and demand forecasting for the IEEE 33-bus system, economic dispatch optimization, and the subsequent analysis and validation of performance metrics. A detailed description of the algorithm developed to address the optimization problem is presented below.
Step 1: Start
Step 2: Data collection and processing
• Power demand, and generation (monthly and hourly profile)
• Environmental variables (temperature, radiation)
• Characterize the distribution network (topology, R, X, Z, length, load, voltage)
• GPV sizing (selection of the photovoltaic panel (Icc, Voc, Pmax, energy to be supplied)
• Calculation and efficiency (temperature losses)
• Levelized Cost of Energy (LCOE)
Step 3: Load Simulation and Electrical Demand Forecasting (IEEE 33 System)
• VAR model (medium-term power forecasting)
• Load flow simulation with Matpower (Voltage profile, power losses, system demand)
Step 4: Economic dispatch
• Objective function (Min. generation costs)
• Decision variables (power generated by diesel and photovoltaic)
• Restrictions (power balance, voltage limits, generation capacity)
• Running simulations without DG (baseline System Performance)
• Optimal location of DG (criticality index based on power losses and voltage profiles)
• Simulations (integration of DG into the distribution system)
• Solving the optimization problem (continuous quadratic programming, Python, and the IPOPT solver)
Step 5: Results analysis
• Reduction in network losses, improvement in voltage profiles, reduction in CO₂ emissions, and reduction in operating costs
• Comparison of scenarios, validation of system efficiency and sustainability
Step 6: End
2.1 Problem formulation
Isolated communities largely depend on diesel-based generation systems, which are characterized by high operational costs and significant CO₂ emissions, thus compromising their long-term sustainability and economic feasibility. The incorporation of renewable energy sources, particularly solar generation, emerges as a promising alternative; nevertheless, the inherent variability of these resources, coupled with fluctuations in electricity demand, complicates efficient energy dispatch planning. Traditional approaches often treat demand as a static parameter or rely solely on historical consumption patterns, disregarding the socioeconomic dynamics that influence energy use and growth. Such simplifications may result in suboptimal allocation of resources and partial exploitation of the renewable generation potential already installed.
In response to these limitations, the present study proposes an optimization framework that integrates demand forecasting with socioeconomic indicators to deliver a more comprehensive and context-sensitive modeling approach for isolated systems. by employing vector autoregression techniques and computational simulations, the model enhances operational efficiency while enabling measurable reductions in both costs and CO₂ emissions. Ultimately, this approach supports more resilient and sustainable energy planning, contributing to the gradual transition toward cleaner and more reliable distributed generation schemes.
2.1.1 VAR model (Vector Auto Regressive)
A VAR model is a model constructed from reduced form simultaneous equations without constraints. The procedure is applied to examine the behavior of a variable, Y, through a group of variables X. This model produces a correlation with more than one variable, and they are related linearly
(1)
(2)
(3)
2.1.2 Active and reactive power losses
The sum of the active and reactive losses in each branch, as explained in (4) and (5),can be used to calculate the total active and reactive energy loss in distribution networks.
(4)
(5)
Where Ploss is the total active power loss, br is the branch location, 𝑛𝑏𝑟 represents the number of branches, 𝐼𝑏𝑟 is the series current flowing through the branch, and 𝑅𝑏𝑟 is the resistance of the branch, Qloss refers to the total reactive power loss, 𝑋𝑏𝑟 is the reactance of that branch.
2.1.3 Solar cell power losses
The power losses of the solar generator due to the effect of the surrounding temperature on the solar cell surface are explained by (6). As explained in (7) a solar cell's efficiency tends to decline with increasing temperature. This is because heat has a detrimental effect on the cell's ability to produce energy
Where, 𝛥𝛲ce𝜄 is the variation of the power output, 𝛲ce𝜄 stc is the nominal power of the cell, 𝛶 is the thermal coefficient of power of the cell, The solar cell's temperature is denoted by 𝑇ce𝜄 the ambient temperature by 𝑇𝑎, 𝐺 is the solar radiation, and the thermal coefficient under non-standard conditions by 𝑁𝑂𝐶𝑇.
2.1.4 Associated costs of thermal generation
The cost function of the diesel generator is modeled using a quadratic equation (8)
(8)
2.1.5 Costs associated with PV generation
The costs of implementation, operation, and maintenance of photovoltaic generation are detailed in (9)
(9)
2.2 Mathematical model
2.2.1 Objective function – minimize total generation costs
The mathematical model consists of an objective function and a set of constraints that ensure compliance with the system's operational requirements. It also ensures that electricity demand is met over a 24-hour horizon, taking into account load variability, technical losses, and fluctuations in environmental conditions. The key elements that make up the model are detailed in (10).
(10)
2.2.2 Restriction: power balance
They refer to the balance of production of each thermal unit equation (11) taking into account that total production is adequate to cover the needs of the electrical system for over 24 hours.
(11)
2.2.3 Restriction: power limits in thermal generation
Equations (12) and (13) refer to the upper and lower limits of the power of each thermal generator, ensuring that the capacities and operating requirements are respected.
(12)
(13)
2.2.4 Restriction: voltage limit
The acceptable voltage limits within the requirement are established by standards and engineering criteria as detailed in (14)
(14)
2.3 Test and simulation system
To carry out the simulations, the 33-node IEEE models, widely used in power flow studies and optimization in distribution networks, were used. However, these systems were modified to incorporate four diesel generators, three of 2000 kW and one of 1250 kW, all connected to node 1 (slack), to replicate the conditions of the generation system of the municipality of Inírida, in the department of Guainía, Colombia. This region is classified as a Non-Interconnected Zone
| Variable | Value |
| Nodes | 33 |
| Branches | 32 |
| Generator | 4 |
| Load | 32 |
| Voltage (kV) | 12.66 |
| Gen set (kW) | 7250 |
Figure 1 shows the modified diagram of the IEEE 33-bus test system. The total system load is 3715 kW and 2300 kVAr. Four diesel generator sets were incorporated for the generation system, achieving a total capacity of 7250 kW. The total power losses are 203 kW and 143 kVAr.
2.3.1 Simulation scenarios
This study analyzes the medium-term power projection and economic dispatch of thermal plants. The proposed scenarios seek to evaluate technical losses, voltage profile, CO₂ emissions, and operating costs. Six scenarios are developed, starting with the baseline scenario without DG, and then progressively integrating PV generation. The scenarios are described in Table 2.
| Case 1 | Scenario | SourcePV | Power capacityPV (kWp) |
| Demand | 0 | Without PV | 0 |
| Forecast 2029 | 1 | 1(PV) | 100 |
| IEEE bus | 2 | 2(PV) | 200 |
| System | 3 | 3(PV) | 300 |
| 4 | 4(PV) | 400 | |
| 5 | 5(PV) | 500 |
2.3.2 Solar module selection and levelized cost of energy (LCOE)
The selected solar panel is the Hiku6 model, which belongs to the Canadian Solar brand, characterized by its monocrystalline structure and a maximum power of 550 Wp. The solar generator capacity is set at 100.2 kWp, based on a daily demand of 405.94 kWh.
This calculation considers an operating period between 6:00 a.m., and 6:00 p.m., ensuring sufficient generation to meet the system's energy needs. One important metric for assessing a generating system's economic feasibility is the levelized cost of energy (LCOE), as it integrates the initial investment, operating, administrative, and maintenance costs, as well as the energy produced over its lifetime
| Solar module selection | Electrical data | Photovoltaic Generation Sizing | Electrical data |
| Reference - Canadian Solar HiKu6 Mono PERC | Peak Solar Hour (PSH) - Inírida Region | 4.05 | |
| Maximum rated power (Pmax) - W | 550 | Energy available per day (kWh/d) | 405.94 |
| Operating voltage (Vmp) - V | 41.7 | Maximum power of the PV generation system (kWp) | 100.2 |
| Operating current (Imp) - A | 13.2 | Module power (Wp) | 550 |
| Open circuit voltage STC- (Voc) - V | 49.6 | Number of photovoltaic modules (un) | 182.2 |
| Short circuit current- (Isc) - A | 14 | LCOE (Levelized Cost of Energy)LCOE= CAPEX+OPEX/Energy Life Cycle (USD/kWh) | 0.068 |
| Module efficiency - % | 21.5 | ||
| Temperature STC - °C | 25 | ||
| Nominal temperature of the operation module °C +-3 | 42.0 | ||
| Temperature coefficient (Pmax) %/°C | -0.34 | ||
| Temperature coefficient (Voc) %/°C | -0.26 | ||
| Temperature coefficient (Isc) %/°C | 0.05 | ||
| Minimum temperature recorded in the areas °C | 20 | ||
2.3.3 Solar cell temperature
As shown in Figure 2, when the ambient temperature rises above 38.2°C, the solar cell can reach a temperature of approximately 67.9°C. This observation highlights the strong dependency of panel efficiency on thermal conditions. As the cell temperature increases, the overall system performance declines, with efficiency levels stabilizing around 85%, thereby confirming the notable impact of temperature on photovoltaic operation.
2.3.4 Energy demand forecast
This section presents the electric power demand forecasting technique based on the Vector Autoregression (VAR) method. The database used includes monthly records from January 2010 to December 2023, as detailed in Figure 3.
For the analysis of electricity demand forecasts, key econometric variables were used, such as the region's GDP, population, and fuel costs. The database used corresponds to the municipality of Inírida, located in the department of Guainía, Colombia. The purpose of the multicriteria model developed is to identify the most efficient technique for selecting the most relevant variables. To this end, statistical variable selection methods were applied, including backward, forward, and stepwise approaches. Table 4 shows the results of the VAR model.
| Indicator | Value | Interpretation |
| Multiple correlation coefficient | 0.975 | It indicates a very strong relationship between the explanatory variables and the dependent variable. |
| Coefficient of determination (R²) | 0.951 | Explains 95.1% of the variability in electricity demand through GDP, population, and fuel price variables. |
| Adjusted R² | 0.935 | Adjusts for the number of variables in the model, maintaining high explanatory power. |
| Standard error | 785.02 | The model shows a moderate average deviation in the predictions. |
| F-statistic | 58.15 | It indicates that the overall model is statistically significant (p < 0,001). |
| Significant variable | Population (p = 0.034) | Population has a positive and statistically significant effect on electricity demand. |
| Variables with low significance | GDP and fuel price (p > 0.05) | Their effect is less decisive within the 95% confidence interval. |
The VAR model demonstrates strong statistical performance, with a multiple correlation coefficient of 0.975 and an R² of 0.95, indicating that 95% of the variability in energy demand is explained by the selected variables. The adjusted R² value of 0.93 indicates that the model exhibits strong explanatory capacity relative to the sample size. The ANOVA results (F = 58.15; p < 0.001) further confirm the overall statistical validity of the model. Among the explanatory variables, population emerges as a positive and statistically significant determinant (p = 0.034), underscoring its direct impact on energy demand. In contrast, GDP and fuel price, although not statistically significant (p > 0.05), display coherent and stable relationships with the dependent variable. The sensitivity analysis reinforces these findings by identifying population as the primary driver influencing future demand projections. Taken together, these results demonstrate that the VAR model is both statistically robust and theoretically coherent, making it an appropriate tool for examining energy demand dynamics in NIZ.
The VAR model was implemented to estimate the evolution of electricity demand over a 60-month period. The results show that, by 2029, demand will increase by 18.2%, as detailed in Figure 4.
With this projection, we evaluate the hourly power demand of the test system, considering its maximum power. Figure 5 shows the projection for the IEEE 33-node test model, highlighting a peak demand of 4397 kW. This information allows us to analyze the system's performance throughout the study period.
2.3.5 Location criteria for distributed generation
The selection of nodes for the DG installation was based on a criticality index (CI) that considers the highest power losses and the lowest voltage profile value recorded in the IEEE 33 test model. The power losses and voltage profiles were evaluated with Matpower version 7.1. Table 5 shows the location of the DG, indicating the selected nodes and the values associated with the power losses, voltage levels, and the criticality index.
| DG node location | Ploss IEEE33 | Voltage p.u. | Critical Index (CI) |
| 6 | 55 | 0.940 | 3.30 |
| 3 | 74 | 0.980 | 1.48 |
| 28 | 16 | 0.920 | 1.28 |
| 5 | 27 | 0.962 | 1.02 |
| 29 | 11 | 0.911 | 0.97 |
2.3.6 Fuel input and output cost function
In this study, the QSK60-G6 and KTA50-G3 diesel generators, with nominal powers of 2500 kVA and 1578 kVA, are used as references. They are part of the generation system of the municipality of Inírida, Colombia. The fuel input and output cost functions of these machines are analyzed to determine their impact on operational efficiency and cost reduction in power generation. The cost functions of each machine are detailed in Table 6.
| Reference | Gen. Set | Cost function |
| QSK60-G6 | 2500 kVA | Y=6E-6X^2 + 0.1398X + 28.012 |
| KTA50-G3 | 1578 kVA | Y=1E-6X^2 + 0.1478X + 15.004 |
This analysis includes the incorporation of photovoltaic DG into the modified IEEE 33-node model. The results are evaluated in terms of generation cost reduction, technical power losses, fuel consumption, voltage profiles, and CO2 emissions, among other aspects.
3.1 Scenario evaluation - IEEE 33-node test system
In Table 7, the results of the performance of the optimization model applied to the economic dispatch of generation are analyzed and evaluated.
| Scenario | Source PV | Power capacity (kWp) | Generation cost(USD) | Ploss (kW) | Energy Gen set (kW) | DG contribution to grid (kWh) | Fuel consumption (gal) | CO2 emissions (kg) | Nodes locateDG |
| 0 | Without GD | 0 | $ 15853.82 | 292 | 92027.3 | 0 | 6222.9 | 61717.8 | 0 |
| 1 | 1 (PV) | 100 | $ 14842.48 | 282 | 91128.7 | 849.84 | 5826.0 | 57780.7 | 6 |
| 2 | 2 (PV) | 200 | $ 13811.68 | 278 | 90100.0 | 1699.68 | 5421.4 | 53767.9 | 6, 3 |
| 3 | 3 (PV) | 300 | $ 12790.96 | 264 | 89136.3 | 2549.52 | 5020.7 | 49794.3 | 6, 3, 28 |
| 4 | 4 (PV) | 400 | $ 11775.37 | 257 | 88205.2 | 3399.36 | 4622.1 | 45840.7 | 6, 3, 28, 5 |
| 5 | 5 (PV) | 500 | $ 10769.82 | 243 | 87339.1 | 4249.20 | 4227.4 | 41926.1 | 6, 3, 28, 5, 29 |
3.1.1 Base scenario without integrating DG
The baseline scenario represents grid operation without distributed generation integration. In this case, all energy is supplied by diesel generators, with CO₂ emissions of 61 717.8 kg and a daily fuel consumption of 6 223.0 gallons. Generation costs reach USD 15 853.83 per day, while power losses amount to 292 kW.
3.1.2 Scenario with DG integration
Fuel consumption and CO2 emissions: The incorporation of PV generation demonstrates a significant decrease in diesel power generation. As shown in Figure 6, a reduction in fuel consumption and CO2 emissions is detailed. In Scenario 1, the energy supplied by the diesel generators is 91 128.7 kWh, implying a daily consumption of 5 826.0 gallons of fuel and a reduction in CO2 emissions to 57 780.7 kg, achieving a contribution of 6.4 % in the reduction of emissions. In scenario 3, CO₂ emissions are reduced to 49 794.3 kg, while fuel consumption decreases to 5 020.8 gallons per day. The energy supplied by the diesel generators is 89 136.4 kWh per day. In scenario 5, CO₂ emissions are reduced to 41 926.1 kg and fuel consumption to 4 227.4 gallons per day. Daily generation from the generator sets decreases to 87 339.1 kWh.
Voltage profile with DG integration: DG plays a fundamental role in electrical distribution networks. It positively impacts voltage profiles, minimizing them and improving the quality of the electricity supply. Figure 7 shows the voltage profiles in the IEEE 33-node test system. It is evident that the progressive incorporation of DG significantly improves voltage levels, increasing from 11 390 V to 11 533.3 V at some points, ensuring compliance with regulatory standards.
Generation costs and power losses: The results of scenarios 1, 3, and 5 are shown to illustrate this behavior. Figure 8 shows that, as distributed generation is gradually integrated at the selected nodes, generation costs decrease steadily. Figure 9 also reveals that power losses in the test system have decreased.
In Scenario 1, with an installed capacity of 100 kW of photovoltaic (PV) generation, generation costs are reduced to USD 14 842.48, while power losses decrease to 282 kW. In scenario 3, with 300 kW of photovoltaic generation, generation costs decrease to USD 12 790.96, with power losses of 264 kW. This scenario represents a 19.3% contribution to generation costs. In scenario 5, where the photovoltaic capacity is 500 kW, generation costs drop to USD 10 769.82 and power losses decrease to 243 kW. This helps reduce energy production costs by 32.1%.
Contribution of photovoltaic generation to distribution networks: Integrating distributed photovoltaic energy generation into distribution networks represents a significant energy contribution. In Scenario 1, distributed photovoltaic generation delivers 849.8 kWh of energy to the distribution network, as illustrated in Figure 10. This contribution represents a small decrease in the use of diesel, with a decrease of 0.98% in thermal generation.
In Scenario 2, the distribution grid receives 1 699.7 kWh of energy from distributed photovoltaic generation. As shown in Figure 11, this integration enables a 2.09% reduction in diesel thermal generation, indicating a moderate amount of distributed generation in the energy mix.
In Scenario 3, as shown in Figure 12, 2 549.5 kWh of energy are injected into the distribution system by photovoltaic distributed generation. In this instance, DG's involvement enables a 3.14% reduction in thermal generation, demonstrating a moderate contribution to the decrease in fossil fuel consumption. In Scenario 4, Figure 13 illustrates how 3 399.2 kWh of energy are contributed to the electrical grid by distributed photovoltaic generation. By reducing thermal generation by 4.15 %, this contribution amounts to a negligible decrease in diesel fuel consumption. In Scenario 5, the distribution grid receives 4 249.2 kWh of energy from distributed photovoltaic generation. As seen in Figure 14, this integration enables a 5.09% decrease in diesel thermal generation, indicating a moderate amount of distributed generation in the energy mix.
Hybrid generation cost curve: Figure 15 illustrates how the generation cost curve gradually drops as the DG share rises, culminating in a reduction of 32.1% in the final scenario. These findings show the financial advantages of DG integration when compared to the base diesel generation curve.
The results of this research indicate that optimizing the economic dispatch of diesel photovoltaic hybrid systems leads to significant reductions in both operating costs and CO₂ emissions in non-interconnected regions. These findings align with previous studies, such as
Furthermore, compared with the study in
While the multi-agent framework and stochastic dynamic programming proposed in
Additionally, the inclusion of socioeconomic variables such as population growth, consumption behavior, and economic activity indicators aligns with evidence presented in
Moreover, the results show that integrating photovoltaic generation helps reduce technical losses and emissions, consistent with recent research on hybrid systems for decarbonizing remote regions
Overall, this research helps bridge an important gap in the literature, as many previous studies have addressed economic dispatch from a purely technical perspective, often overlooking the influence of socioeconomic variables on energy planning. This study demonstrates that incorporating such variables not only enhances forecasting accuracy but also supports more equitable and sustainable strategies for isolated communities. In doing so, it provides a methodological foundation to strengthen public policy development focused on sustainable energy supply planning.
3.1.3 Limitations
Although this research has achieved significant progress, certain limitations must be acknowledged to provide a realistic perspective on its scope. One of the main challenges lies in the availability and reliability of data, since information on energy consumption and local economic dynamics in isolated communities is often scarce or inconsistently recorded. To address this issue, historical datasets were employed; however, the precision of the model may still be influenced by the quality and completeness of the available information.
Another relevant aspect concerns the need for pilot implementations and context-specific calibration prior to the application of the optimization model in real environments. The model’s performance largely depends on its capacity to adapt to the unique characteristics of each community, which may require additional methodological refinement.
Moreover, this study did not explore in depth the influence of human factors, such as community acceptance of the proposed model or the level of technical expertise within local populations elements that could considerably affect the success of future implementations. In addition, while the model integrates photovoltaic generation, it provides only a limited examination of energy storage management. Previous research has shown that incorporating battery systems can substantially enhance network stability and decrease operational costs in hybrid diesel renewable configurations, highlighting an area that warrants further investigation
Finally, future developments could benefit from the integration of advanced machine learning algorithms to improve forecasting precision, as well as multi-objective optimization strategies capable of simultaneously addressing economic, environmental, and reliability considerations.
The results of this research reveal that optimizing the economic dispatch of hybrid diesel photovoltaic systems in isolated communities leads to notable reductions in both operating costs and CO₂ emissions, while simultaneously enhancing the overall efficiency and sustainability of the energy supply. The incorporation of vector autoregressive models for demand forecasting, combined with computational simulations, made it possible to design a more precise and context-specific model that reflects real consumption dynamics in remote areas.
Depending on the degree of renewable energy penetration, the optimization process can reduce generation costs by up to 32.2%. Likewise, when fuel consumption reaches 4 320.4 gal/day, CO₂ emissions decrease by approximately 42 848.9 kg. Improvements were also observed in voltage quality as distributed generation was gradually integrated, increasing voltage levels from 11 390 V to 11 533.3 V in certain nodes. This enhancement reduces the unnecessary operation of diesel generators and promotes greater use of renewable sources.
The study successfully fulfilled its main objective: to develop and assess an optimal dispatch model for hybrid diesel–photovoltaic generation that increases system efficiency while minimizing operational costs and emissions in non-interconnected regions. The proposed methodology not only optimizes energy generation but also incorporates socioeconomic considerations into dispatch planning. Unlike earlier approaches that concentrated solely on technical parameters, this research emphasizes the relevance of including economic and social variables in the management of energy demand, thus providing a more comprehensive framework applicable to real-world scenarios.
Furthermore, implementing the optimization model under different simulated conditions allowed an evaluation of thermal generation behavior and projected demand patterns, generating valuable insights for strategic decision-making in energy planning and system operation. Future research may build upon this framework by integrating advanced machine learning algorithms, such as recurrent neural networks, to further refine demand forecasting accuracy.
Finally, pilot applications in real communities are encouraged to assess the practical viability of the model and to explore funding mechanisms that support its implementation in vulnerable regions. Overall, this work advances efficient energy planning and management in isolated communities, offering an innovative and adaptable pathway for sustainable energy optimization in future studies.
The article did not receive financial support from any funding agency, organization, or institution, public or private.
The authors declare that they have no conflict of interest.
Carlos Arturo Páez: Conceptualization, Methodology, Research, Formal Analysis, Validation, Document Writing, Document Editing, and Supervision.